HVAC/R Internal Sealants | Kitchener ON

HVAC/R Internal Sealants | Kitchener ON


Gary McCreadie is an HVAC tech, the creator of hvacknowitall.com and the HVAC Know It All Podcast


 

Confession 

I have a confession to make, yes, I use internal sealants.  I guess you’re going to have to keep reading to understand why.  

Internal sealants in the HVAC/R industry have been given a bad rap, rightfully so, as the older polymer based sealants would react to moisture and air and be the cause of potential system blockages.  There were also technicians that would ignore the process of a system leak check and add a can of sealant without much of a diagnosis, this actually still happens quite often but I’m here to help with a little education.

 

Service call on a frozen coil 

 

The Right Approach

Before we get into using a leak sealant product, we need to understand a few things first, is there a leak?  Where is the leak?  Is it repairable in a cost effective way?  If a technician first discovers the system is short of refrigerant, it’s not acceptable to add leak sealant and walk.  The technician should perform a leak inspection, my suggestion is with an electronic leak detector, and then with soap to verify its presence, most leak detectors can pick up a very low leak rate, so in some cases, bubbles may not appear.  In the right circumstance dye can be used, as I stated, in the right circumstance it is actually very effective, especially in thicker evaporator coils that contain 5 rows or more.  

 

 

Once the leak is found, determine if the repair can be performed in the traditional manner, brazing or cutting off and re-flaring a bad flare joint for example.  If you happen to find a leak in a porous evaporator, most likely the copper within the coil has succumb to formicary corrosion and has become relatively fragile.  Cutting into a coil in this condition to access the leak point can lead to more leaks, especially if the coil is in bad shape.  At this point, a coil replacement is your best bet for a successful repair.  

Butchering into an old coil and spending time to do so, may not be so cost effective to the customer, this you’ll have to judge for yourself and as I stated above could cause more damage to an already fragile hunk of metal.    

Sometimes, the system is critical, or the coil is not available and the customer needs to be up and running yesterday.  This is where a trained technician that is educated on various options available may use an internal sealant.  Remember, installing a sealant is a customer option that should be explored in the “correct” scenario and application to get a system up and running again.  

 

Product Testing 

This is where I’m going to be biased, only because I have tested this product in many different applications, ranging from walk-in boxes to reach-ins to a Liebert unit inside of a small data center.  December of 2017 was the first time I used AC Smart Seal.  Since, I’ve used it 10-15 times, all units were well out of warranty and had leaking evaporators.  I can report that not one system has had a failed compressor or blocked metering device.  The simple reason is that the product is an oil based formula, not polymer based.  Furthermore, as per the manufacturer, it doesn’t react to air or moisture, in fact it’s inert and non-reactive.  It acts mechanically, as refrigerant is forced from the leak site, the oil based sealant is dragged along with it, for lack of a better phrase, and the elastic molecules begin to aggregate creating a seal. 

Does it work in every situation, no!  The leak needs to be small enough for it to work.  If you notice a large leak on a braze joint, repair it, simple and plain.  If you’re dealing with a seasonal mystery leak or find that a corroded evaporator coil is contributing to your problem.  An internal leak sealant could be a candidate.  It will give you a runway of operation until a more suited repair can be made, or scheduled depending on the nature of the application.  

 

Listen to an old school episode of the HVAC Know It All Podcast discussing internal sealants

 

Case Study

Early in 2021, I found a frozen evaporator coil on a Liebert unit.  I allowed it to thaw and determined the system was short on refrigerant charge, we had a leak.  The system had dye previously added many years prior and my leak detector was sensing a leak in and around the evaporator.  Due to the size of the coil and location of the leak, soap wasn’t going to work to pinpoint the location.  I used a black light and discovered a very small leak.  Again, due to location not exactly fixable in a cost effective way.  Because of the age of the machine, I talked about replacement with the customer, but in the meantime they were on board with trying out a sealant.  I educated the customer on my past experience with AC Smart Seal and they had nothing lose at this point.  

 

Diagnoses to determine the system was low on refrigerant charge

 

Addition of AC Smart Seal 

System operation after addition of refrigerant charge and TX valve adjustment

 

I added the sealant and then charged the system using superheat and subcooling as my guide.  I returned a few months later to check on the system and it was still functioning with a full charge.  I used my leak detector in the same area it had registered a leak on my previous visit and it didn’t pick up anything.  I was also back there a few days prior to writing this article and the charge was still good.  

 



 

In Conclusion 

The purists may not agree, but these tests that I have conducted over the last four years in various applications have revealed zero system failures and in the above case, showed no detection of a refrigerant leak post use of the sealant.  Verification of a leak and finding the leak is essential to the process, education of and testing of the product is a must.  Next, the application must fit, in this case, a very small “unrepairable” type leak was the perfect candidate.   

 

Gary McCreadie

Subscribe to the HVAC Know It All app 

Follow HVAC Know It All on Instagram, Facebook, YouTube and LinkedIn and LISTEN to the HVAC Know It All Podcast

Save 8% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)

Save 8% at eMotors Direct with code HVACKNOWITALL

 



Whether you require installation, repair, or maintenance, our technicians will assist you with top-quality service at any time of the day or night. Take comfort in knowing your indoor air quality is the best it can be with MOE heating & cooling services Ontario's solution for heating, air conditioning, and ventilation that’s cooler than the rest.
Contact us to schedule a visit. Our qualified team of technicians, are always ready to help you and guide you for heating and cooling issues. Weather you want to replace an old furnace or install a brand new air conditioner, we are here to help you. Our main office is at Kitchener but we can service most of Ontario's cities


Source link

Add Comment

Your email address will not be published. Required fields are marked *