Best Practices to Conserve A2L Refrigerants in a Shortage

Best Practices to Conserve A2L Refrigerants in a Shortage


If you own your HVAC company or are involved in management, you may have realized that our industry is currently facing a shortage of new A2L refrigerants, particularly R-454B and R-32.   

Our own company has faced limited availability and long lead times, mainly due to supply chain disruptions and the increased demand now that our industry is primarily installing new systems with these A2L refrigerants. (According to ACHR NEWS, there is a shortage of cylinders that meet the required safety criteria for A2Ls, not a shortage of the actual refrigerant. You can read that article here.)   

Due to the shortage, prices have risen and will likely continue to do so, at least in the short term. The costs get passed along to our customers, and that’s something we want to mitigate as much as possible. This tech tip will share our company’s current plan to help our techs conserve R-454B whenever they’re on the job.  

 

Tank Usage: Documentation, Documentation, Documentation  

First and foremost, we need to document the use of refrigerant within the company so that we can track how it’s being used and eliminate waste.  

At our company, all of our cylinders in use are tagged — both virgin refrigerant and recovery tanks. Our techs document how much refrigerant they use and recover, respectively, for safety and procurement purposes.  

Every technician is required to write down the job number and how much refrigerant was used on the tag. This practice also encourages accountability and gives us a record of what was charged or recovered in case we get callbacks related to undercharge or overcharge.  

 

Training for a Zero-Leak Policy  

In an ideal world, there would be no leaks, and even if there were leaks, every leak would be found, confirmed, and patched without a hitch. Unfortunately, that’s not exactly realistic.  

Thorough nitrogen pressure testing, evacuation, and leak detection are the keys here, as is a solid visual inspection. Each time we braze, we should be checking joints and connections to look for any possible leaks or imperfections — that means using a mirror to see behind and underneath the tubing, too.   

We’re not going to get too deep into this topic since we have a comprehensive article about leak detection and mitigation, but the bottom line is that the system needs to be able to hold steady whenever you pressurize it with nitrogen (the exact pressure should be on the equipment data plate).  

(Courtesy of Bryan Orr)

Residential systems up to 5 tons can usually do fine with pressure tests lasting 30-60 minutes, but we’ve asked our techs to make them last an hour. When you have larger equipment with more refrigerant, such as in light commercial settings, you may need to perform a longer pressure test. (On top of that, if the manufacturer calls for a specific duration, you’ll want to follow their instructions.) In refrigeration, the systems are so large that pressure tests may take 24 hours or more.   

During the course of a pressure test, there may be significant changes in the ambient temperature, and you don’t want to mistake pressure changes due to temperature for leaks. You can use calculators like our Nitrogen Pressure Calculator in these situations.   

nitrogen pressure change.

(Courtesy of Bryan Orr)

 

Deep Vacuums — With Documentation  

Evacuation gets all of the air, moisture, and non-condensable gases out of the refrigerant tubing. A deep vacuum ensures that a refrigerant is clean, dry, and tight, which reduces the risk of oil contamination and can also confirm whether a system is leak-free.  

Our process is to pull a deep vacuum below 300 microns on brand-new systems and at least 500 microns on systems that have been in service. Within 10 minutes, we don’t want to see the vacuum decay to above 500 microns or 1000 microns, respectively.  

Apps like measureQuick, MyNAVAC, and BluVac may also monitor your decay tests for easy documentation. The system’s behavior under deep vacuum can also tell you if you have a wet or leaky system; a wet system will have a sharp rise and then level off, and a leaky system will have a continuous rise.  

leak free.

(Courtesy of Bryan Orr)

Having a procedure in place for techs to document decay test results, as with the refrigerant usage, also promotes transparency and accountability whenever there are refrigerant-related callbacks.  

 

Always Use a Charging Scale and Allow Ample Time for Readings to Stabilize  

With leak detection and evacuation out of the way, we can focus on the charging part of the equation.  

Whenever we charge or recover refrigerant, we should absolutely use a charging scale. Not just “when in doubt, weigh it out,” but anytime we use these A2Ls. Whenever you’re dealing with long line sets, you can use a calculator (again, like our Additional Charge Weight Calculator) to dial in the extra charge as accurately as possible.    

additional charge weight.

(Courtesy of Bryan Orr)

On top of that, allow some time for your temperature and pressure readings to stabilize, about 10 minutes or so, before adding more refrigerant. The less we have to recover later (ideally nothing), the better, even if it takes a little longer.  

Every pound of refrigerant we lose through leakage isn’t just expensive — it may soon be irreplaceable if the packaging and supply chain issues aren’t resolved. Customers depend on us to keep their systems running; we must use the refrigerant we have wisely.  

Our trainers worked to develop a training program based on leak detection, vacuum, and charging best practices. Below, you can find a list of HVAC School’s free resources in case you want to pull any materials for your company’s training programs. 

Originally published April 26, 2025, at hvacrschool.com. 

Whether you require installation, repair, or maintenance, our technicians will assist you with top-quality service at any time of the day or night. Take comfort in knowing your indoor air quality is the best it can be with MOE heating & cooling services Ontario's solution for heating, air conditioning, and ventilation that’s cooler than the rest.
Contact us to schedule a visit. Our qualified team of technicians, are always ready to help you and guide you for heating and cooling issues. Weather you want to replace an old furnace or install a brand new air conditioner, we are here to help you. Our main office is at Kitchener but we can service most of Ontario's cities