Matthew Showers is an HVAC service technician, performing work in both the residential and commercial fields. His specialty is in inverter and communicating systems. Follow Matt on Instagram
O/B Terminals
As Gary mentioned in a recent podcast, reversing valves are used in heat pumps to direct the flow of refrigerant depending on the demand for heating or cooling. Also mentioned was the fact that reversing valves have a default position when they are not energized. Most manufacturers at this point default to heat (O terminal is energized for cooling), though there are some that still default to cooling (B terminal is energized for heating). Below is a list of manufacturers that use B because it is less common:
- Rheem
- Ruud
- Weathermaker
- Ameristar
- Bosch air source (WSHP uses O)
Another consideration with heat pumps is light commercial systems. Many manufacturers will still use traditional heat pump control wiring for their systems, but a handful actually use conventional wiring, much like you’d see with a gas furnace with AC. The most notable examples that I have encountered are Carrier and York. These systems, regardless of cooling stages, use W1 to energize all compressors for heating and W2 to energize auxiliary heat. This is because on a call for Y1, the control signal goes through the economizer control first (in a RTU application) before potentially energizing the stage one compressor contactor.
W1 then is used to bring on all compressors for heating for a couple reasons: it bypasses this economizer control, ensuring no unnecessary outside air enters the airstream, it brings on all the compressors because we are not concerned about latent heat removal, and it allows the logic board to determine the appropriate reversing valve position. With Carrier specifically, these logic boards are used in tandem with either a defrost board in their heat pumps or an ignition control board for their gas furnace RTUs.
I Would Also Like To Add A Note This
Back in the day, I have work on packaged water cooled heat pumps in ceiling spaces where they used mercury thermostats to control them. These heat pumps failed in heating, so a call for W1 would run the heat pump in heating mode. To run in the cooling mode, they took an interesting approach. A call for Y1 would energize the reversing valve and a call for Y2 would pull in the contactor for the compressor. The building had many heat pumps through out many floors that were wired this way. Gary McCreadie
RTFM
As with any system, the most important thing that anyone can do is to RTFM: read the fantastic manual. This ensures that the system you’re working on is wired and set up properly at the thermostat.
Matthew Showers
Subscribe to the HVAC Know It All app
Follow HVAC Know It All on Instagram, Facebook, YouTube and LinkedIn and LISTEN to the HVAC Know It All Podcast
Save 8% on purchases at TruTech Tools with code knowitall (excluding Fluke and Flir products)
Save 8% at eMotors Direct with code HVACKNOWITALL
Whether you require installation, repair, or maintenance, our technicians will assist you with top-quality service at any time of the day or night. Take comfort in knowing your indoor air quality is the best it can be with MOE heating & cooling services Ontario's solution for heating, air conditioning, and ventilation that’s cooler than the rest.
Contact us to schedule a visit. Our qualified team of technicians, are always ready to help you and guide you for heating and cooling issues. Weather you want to replace an old furnace or install a brand new air conditioner, we are here to help you. Our main office is at Kitchener but we can service most of Ontario's cities
Source link
Add Comment