AHRI Phase II Report Links Nuisance Trips to GFCI Compatibility

AHRI Phase II Report Links Nuisance Trips to GFCI Compatibility


ARLINGTON, Virginia — The Air-Conditioning, Heating, and Refrigeration Institute (AHRI) released its Phase II report examining compatibility between variable-speed HVAC equipment and Ground Fault Circuit Interrupter (GFCI) breakers, concluding that nuisance tripping is primarily caused by the interaction between inverter-driven equipment and the frequency response of individual GFCI devices rather than a universal equipment defect.

According to the report, researchers moved beyond the observational findings from Phase I to identify the electrical mechanisms responsible for nuisance trips required under National Electrical Code (NEC) Section 210.8(F). The study combined frequency-dependent testing of multiple GFCI breaker models with laboratory testing of two inverter-based HVAC systems operating under controlled startup and normal operating conditions.

The report found that GFCI performance varies significantly among breaker models because each device responds differently to higher-frequency leakage currents generated during normal operation of variable-speed HVAC equipment. As a result, one breaker may repeatedly trip on a specific system while another breaker does not, even under similar installation conditions.

Researchers also determined that the greatest likelihood of nuisance tripping occurs during equipment startup rather than during steady-state operation. Extended off-time energization, compressor startup sequences, switching events, and electrical transients were identified as the highest-risk operating conditions.

Testing also revealed that one HVAC system exhibited an additional 60-hertz leakage mechanism during startup related to equipment topology. According to the report, an approved component modification eliminated the condition, allowing researchers to continue evaluating high-frequency leakage characteristics.

The report recommends that AHRI continue working with standards organizations to develop frequency-aware testing methods and interoperability requirements that better reflect the operating characteristics of modern inverter-based HVAC equipment. Researchers also recommend standardized reporting of leakage current characteristics and additional evaluation of transient startup conditions.

For manufacturers, the report recommends characterizing GFCI performance across a broader range of frequencies, improving immunity to non-hazardous high-frequency leakage currents, and expanding pre-market interoperability testing. HVAC equipment manufacturers are encouraged to measure and reduce leakage currents at dominant switching frequencies while refining inverter and filtering designs to minimize common-mode leakage.

According to AHRI, the recommendations are intended to preserve the safety objectives of NEC’s GFCI requirements while improving compatibility with today’s variable-speed HVAC systems.

The current NEC GFCI exemption for outdoor HVAC equipment is set to expire Sept. 1, unless a Tentative Interim Amendment (TIA) request to extend the current 210.8(F) exception to Sept. 1, 2028, is approved.

To view AHRI’s full report, click here. 

Whether you require installation, repair, or maintenance, our technicians will assist you with top-quality service at any time of the day or night. Take comfort in knowing your indoor air quality is the best it can be with MOE heating & cooling services Ontario's solution for heating, air conditioning, and ventilation that’s cooler than the rest.
Contact us to schedule a visit. Our qualified team of technicians, are always ready to help you and guide you for heating and cooling issues. Weather you want to replace an old furnace or install a brand new air conditioner, we are here to help you. Our main office is at Kitchener but we can service most of Ontario's cities